How to use
Enter current, voltage, one-way length and allowed drop. Model: two-conductor DC copper loop.
Worked example
Example: 10 A, 120 V, 50 ft one-way and a 3% drop limit gives 14 AWG for voltage drop. Ampacity still needs a separate check.
What does this result mean?
Smallest listed AWG meeting the voltage-drop limit under these assumptions. It does not check ampacity, breaker sizing, installation conditions or electrical code.
Copper resistivity: 0.017241 Ω·mm²/m at 20°C (NIST). Resistance rises with temperature; AC impedance and wiring details are not modeled.
Educational estimate only. A qualified electrician must verify ampacity, insulation, overcurrent protection, installation method, temperature derating and local code. Inputs stay in this browser.
Reference
NIST Copper Wire Tables (Handbook 100) · Southwire voltage-drop calculator